Applications & Features
- For diff.pressure measurement of compatible fluid and gas
Model & Data
Sensor | glass micro fused silicon strain sensor |
---|---|
Power | Current: 18.5~35VDC (RL=500Ω), 8.5~35VDC (RL=0Ω), Voltage output: 16~35VDC, 16~28VAC |
Output | 4~20mA (2 wires), 0~10VDC(3 wires) or RS485 |
Output Load | ≤500Ω (current), ≥2kΩ (0-10VDC) |
Accuracy | typical ±0.5%FS (BFSL), see range specifications |
Output | 4~20mA (3 wires), 0~10VDC, RS485 / Modbus; OUT1: T, OUT2: CO |
Range | see range specifications |
Display | LCD, with unit indication(kPa/mbar/in WC/bar/MPa)* |
Temp. Limit | work -20~70°C; medium -20~85°C; compensation 0~55°C |
Pressure Limit | see range specifications |
Response time | ≤500ms |
Medium compatibility | 17-4PH stainless steel |
Housing | sensor 17-4PH stainless steel; sensor casing 304 stainless steel enclosure ABS+PC(flame retardant) |
Protection | IP65 |
Weight | 0.6kg (without mounting bracket) |
Approval | CE |
Mount Bracket | PDT-A, for surface mount, should be ordered separately |
*The factory set engineering unit is bar. Customer can switch to others with the UNIT button on the PCB.
Range Specifications
Range | Pressure limits in both side ports | Accuracy | Temperature | |||
---|---|---|---|---|---|---|
Rated | Overload | Burst | (BFSl) | Coefficient | ||
Code | bar | bar | bar | bar | %FS | %FS/°C |
0 | 0~0.5 | 3.5 | 7 | 17.5 | 1.0 | 0.15 |
1 | 0~1 | 3.5 | 7 | 17.5 | 0.5 | 0.1 |
2 | 0~2 | 3.5 | 7 | 17.5 | 0.5 | 0.05 |
3 | 0~4 | 7 | 14 | 35 | 0.5 | 0.05 |
4 | 0~6 | 10 | 20 | 50 | 0.5 | 0.05 |
5 | 0~10 | 10 | 20 | 50 | 0.5 | 0.05 |
6 | 0~10 | 16 | 32 | 80 | 0.5 | 0.05 |
7 | 0~16 | 16 | 32 | 80 | 0.5 | 0.05 |
Models
Models | PDT | Diff. Pressure Transmitter | ||||
Output | CMD | 1
2 8 |
0 ~ 10v
4 ~ 20mA RS485/Modbus RTU |
|||
Range | X | See Range Specifications | ||||
Process Connection |
2 4 5
|
1/4 NPT
G1/4 Others |
||||
Display | 0
1 |
N/A
LCD |