Epdth04111 01

Description

The EPDAF sensing element uses a robust long life ceramic fulcrum lever technology with the patented self-calibration system to guarantee the long-term stability and high performance pressure measurement. The sensor element used in the EPDAF is not affected by any condensation, high humidity or contaminants present in the measure environment.

The EPDAF has built-in electronic circuit, which enables digital measurement of pressure value with temperature compensation logic by continuous monitoring of the sampling air. Built-in calibration routine is integrated in the transmitter electronic circuit. It is ideal for measuring air flow in air condition system, staircase pressurization, lift lobby pressurization and measuring of low air flow in clean room, laboratory, operating theater and isolation room application.

  • Sensor Technology: Ceramic Fulcrum Lever Technology
  • A/D Resolution: 16 bits
  • Sensing Range: – 100 pa to 100 pa & -500 pa to 500 pa
  • Signal Output: 1 x 4-20 mA, four wires connection for measuring or configurable as PID control output & 1 x relay output for floating controller
  • Interchangeability: The transmitter (sensor and electronic) is interchangeable with other same type transmitter
  • Mounting: Wall Mounted
  • LCD Display: Display Different Pressure (pa or mmH2O) and including set point value
  • Communication: 2 wire RS-485
  • Protocol: Modbus RTU
  • Power Supply: 24 Vdc

Electric connections

Hardware Specifications

Power Supply: 12 – 24Vdc
Power Consumption: 6 VA (including transmitters)
Input A/D Resolution: 12 bits
Sensing Range: Temperature (0 – 70 Deg C) and humidity (0 – 100% rh)
Output Signal: 2 x 4~20mA
Accuracy: Temperature (±0.1°C) and humidity (±2%RH)
Response Time: For temperature: 10s (still air) / 10s (with duct 3m/s air speed).
For humidity: 4s (still air) / 4s (with duct 3m/s air speed)
Communication: 2 wire RS-485
Baud Rate: 9600~76.8kbps
Protocol: Modbus RTU
Surge Protection: 15KV ESD for serial port
Operating Condition: 0~+70°C / 0-100% RH, not condensing
Storage Condition: -20~+70°C / 0-100% RH, not condensing
Probe Length: 191 mm
Protection: IP65
Weight: 210 g

Dimensions

Resources

Pdf 300x300 010_CE_SS-1.pdf