4a

Description

The Open Control System Controller is a fully programmable controller that is intended for Building Control System; Environment Control System and HVAC Control Systems. The Controller being fully programmable will ensure control & monitoring application versatility, allowing specific application to be created according to each facility or application requirement. The controller is a fully configurable controller based on the PIC series micro-controller with an on-board clock and two RS-485 communications Bus. The five digital outputs 240VAC relays (7 Amps) are ideal for driving contractors and starters directly. The four analog outputs (0 – 10 VDC or 4 – 20 mA) are used for modulating actuators or dampers or electronic-pneumatic actuators or variable speed drives and other analog actuators. The six digital inputs are be used for pulse counting and reading contact closures directly. The three analog inputs are be used for reading the 10K thermistor, 4 to 20mA and 0 to 10VDC input signals.

  • 10-bit, Analog-to-Digital Converter
  • 8-bit, Digital-to-Analog Converter
  • Power Supply – 24VDC/AC
  • Surface Mount   Device (SMD)
  • Analog Input Monitoring
  • Digital Input Monitoring
  • Maintained / Pulse Digital Output Control
  • Analog Output Modulating Control
  • Optional Demand Limiting Control
  • Logic Based Control
  • Alarm Monitoring
  • Trend Logging

The fact that the controller is fully programmable ensures complete control and monitoring application flexibility. The same standard controller hardware can be used for control and monitoring of the following applications:

  • HVAC, BAS & EMS Systems.
  • Chiller, Heat Pump units and Rooftop units.
  • Other types of programs can be developed according to
    customers’ specifications.

Technical Specifications

Supply Voltage/Power Consumption: 24 VAC or 24 VDC / 10VA (plus loads)
Protection: 1A Fuse
Analog Inputs: 3 x 10K thermistors or 3 x 4 to 20mA or 3 x 0 to 10VDC. Accuracy:
0.1% full scale or 6 x for reading contact closures directly
Digital Inputs: 6 x for reading contact closures directly complete with surge protection (Photocoupler Type)
Analog Outputs: 4 x 0-10VDC or 4 x 0 to 20mA. Resolution: 0.4% full scale
Digital Outputs: 5 x Relay Dry Contacts with contact rating of 240VAC maximum 7Amps (2 Relay Outputs have Normally Open & Normally Close Contact).
Microprocessor: PIC Micro-Controller (128 KB SRAM & 256 KB FLASH)
Communications: 2 x RS-485 Bus (One System Bus & One Controller Bus). Baud

Rate: 9600~76.8Kbps. Maximum Length: 4000 ft (1.2km)

Freely Programmable: Yes, using DLC Software Tool
Indication: 1 x Green LED for Power / 6 x Green LED for Digital Inputs /  4 x Green LED for Digital Outputs
Cover Dimension: 146mm x 114mm x 38mm
Weight: 500g
Ambient limits:
a) Storage: -10 to 90 ºC; less then 90% rh, non-condensing
b) Operating: 0 to 70 ºC; 10 to 90% rh, non-condensing

Controller Physical Dimension

Size: 146mm x 114mm x 38mm

All connections to the Open Control System Controller are via removable plug-in screw terminals for easy installation and servicing. The removable plug-in screw terminals accept wire sizes from 0.5 to 1.5 mm sq. section area cable.