Emr3201001 01

Description

The EMR3201001 sensing element uses a robust long life ceramic fulcrum lever technology / NTC / HIH4000 technology with the patented self-calibration system to guarantee the long-term stability and high performance differential pressure, temperature and humidity measurement. The ceramic fulcrum lever technology / NTC / HIH4000 sensor element used in the EMR3201001 is not affected by any condensation, high humidity or contaminants present in the measure environment.

The EMR3201001 has built-in electronic circuit, which enables digital measurement of differential pressure value with temperature compensation logic by continuous monitoring of the sampling air. Built-in calibration routine is integrated in the transmitter electronic circuit. It is ideal for many domestic and light industrial applications including office, restaurants, classroom, and supermarket.

  • Real-time monitoring of room differential pressure (Dp), temperature (T) & humidity (H)
  • Sensor Element: Ceramic Fulcrum Lever Technology / Temperature – NTC Humidity – HIH4000
  • A/D Resolution: 12 bits
  • Sensing Range: Pressure (-500 – 500 pa) / Temperature (-40 – 150 oC) and Humidity (0 – 100 % rh)
  • Sensor Signal Output: 3 x 4-20 mA, six wires connection for measuring Differential Pressure / Temperature / Humidity
  • Interchangeability: The transmitter (sensor and electronic) is interchangeable with other same type transmitter
  • Mounting: Wall Mounted
  • LCD Display: Display Dp, T, H and including set-point value
  • Communication: 2 wire RS-485
  • Protocol: Modbus RTU
  • Power Supply: 24 Vdc

Electric connections

Hardware Specifications

Power Supply: 24Vdc
Power Consumption: 10 VA
Sensor Element: Ceramic Fulcrum Lever Technology / NTC / HIH4000
Sensor Range: Dp (-500 – 500 pa) / Temp. (-40 – 150 oC) / Humidity (0 – 100% rh)
A/D Resolution: 12 bits
Accuracy: Dp (± 2 pa ±3% of reading) ) / Temp. (±0.1oC) / Humidity (±2% rh)
Repeatability: ± 1% of reading
Long Term Output Drift: < 1% of full scale over the life of the sensor
Digital Output: 2 x for adjustable switching thresholds control (Relay SPST N.O. Dry
Contacts / Rating: 30 Vdc,1A)
Analogue Output: 4 to 20 mA
Microprocessor: PIC microcontroller
Indication / Adjustment: LCD Display plus buttons
Communication / Baud Rate: 2 wire RS-485 Modbus RTU / 9600~76.8kbps
Surge Protection: 15KV ESD for serial port
Operating Condition: 0~+50°C / 5-95% RH, not condensing
Storage Condition: -20~+60°C / 10-90% RH, not condensing
Mounting: Wall mounted
Weight: 300 g

Dimensions